Diseño de un sistema de aprovechamiento de las aguas residuales domesticas de un centro comercial de la ciudad de Guayaquil
Para citar o enlazar este item, por favor use el siguiente identificador:
http://dspace.ups.edu.ec/handle/123456789/27477
Registro completo de metadatos
Campo DC | Valor | Lengua/Idioma |
---|---|---|
dc.contributor.advisor | Ordoñez Ramírez, Virgilio Alonso | - |
dc.contributor.author | Cano Moreira, Nery Alejandro | - |
dc.date.accessioned | 2024-03-27T20:17:43Z | - |
dc.date.available | 2024-03-27T20:17:43Z | - |
dc.date.issued | 2024 | - |
dc.identifier.uri | http://dspace.ups.edu.ec/handle/123456789/27477 | - |
dc.description | La investigación tiene por objeto el diseñar un sistema de tratamiento de las aguas residuales domésticas de un centro comercial en la ciudad de Guayaquil. El procedimiento realizado consistió en la caracterización inicial del sistema de tratamiento existente, siendo que el centro comercial posee cuatro tipos de actividades generadoras de efluentes: las de restaurante, las de tiendas comerciales, las de servicios higiénicos y mantenimiento y las del área de parqueo, constituyendo su sistema de tratamiento actual en sistemas subsecuentes de trampa de grasas; al analizar el efluente generado y el cumplimiento de la normativa vigente se verifico que los efluentes únicamente cumplen con los centro de descarga de Potencial de Hidrógeno, Temperatura y Sólidos Totales; posteriormente se procedió a la realización de la prueba de jarras aplicando una corrección de pH con 20 ml de solución de cal de concentración al 1% y diferentes dosis de Sulfato de aluminio al 1% (2 ml, 3 ml, 4 ml, 5 ml, 6 ml, 7 ml, 6.5 ml y 7.5 ml), aplicando el Índice Wilcomb, dando como resultado que la dosis que obtuvo el mejor resultado fue 7 ml. Se realizó la comprobación de hipótesis con la aplicación de la T de Student dando como resultado que la mejor dosis, luego de pasar por un proceso de filtración, además de cumplir con los limites permisibles de descarga, tiene diferencias significativas en la eficiencia del tratamiento en comparación con el testigo y la muestra sin filtrar. Considerando que el centro comercial general un caudal mínimo de 41 m3/día y un valor máximo de 65 m3/día, con un valor promedio de 52.98 m3/día y 1609.00 m3/mes se propone un sistema de aprovechamiento que permitirá descargar el efluente cumpliendo con la normativa vigente y permitiendo aprovechar el agua tratada como agua de riego de áreas verdes. | spa |
dc.description.abstract | The objective of the research is the design of a domestic wastewater treatment system from a shopping center in the city of Guayaquil. The procedure carried out consisted of the initial characterization of the existing treatment system, since the shopping center has four types of effluent-generating activities: restaurants, commercial stores, hygienic services and maintenance, and parking areas. constituting your current treatment system into subsequent grease trap systems; When analyzing the effluent generated and the regulatory compliance with the current one, it is verified that the effluents only comply with the discharge centers of Hydrogen Potential, Temperature and Total Solids; Subsequently, the jar test was carried out by applying a pH correction with 20 ml of lime solution with a 1% concentration and different doses of 1% aluminum sulfate (2 ml, 3 ml, 4 ml, 5 ml , 6 ml, 7 ml, 6.5 ml and 7.5 ml), applying the Wilcomb Index, resulting in the dose that obtained the best result was 7 ml. The hypothesis testing was carried out with the application of Student's T, resulting in the best dose, after going through a filtration process, in addition to complying with the permissible discharge limits, has significant differences in the efficiency of the treatment in comparison with the control and the unfiltered sample. Considering that the shopping center generates a minimum flow of 41 m3/day and a maximum value of 65 m3/day, with an average value of 52.98 m3/day and 1609.00 m3/month, a utilization system is proposed that will allow the effluent to be discharged in compliance with with current regulations and allowing the treated water to be used as irrigation water for green areas. | spa |
dc.language.iso | spa | spa |
dc.rights | openAccess | spa |
dc.rights | Atribución-NoComercial-SinDerivadas 3.0 Ecuador | * |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/3.0/ec/ | * |
dc.subject | CARACTERIZACIÓN DE AGUAS RESIDUALES | spa |
dc.subject | PRUEBA DE JARRAS | spa |
dc.subject | LÍMITES PERMISIBLES | spa |
dc.title | Diseño de un sistema de aprovechamiento de las aguas residuales domesticas de un centro comercial de la ciudad de Guayaquil | spa |
dc.type | bachelorThesis | spa |
ups.carrera | Ingeniería Ambiental | spa |
ups.sede | Sede Guayaquil | spa |
Pertenece a las colecciones: | Grado |
Ficheros en este ítem:
Fichero | Descripción | Tamaño | Formato | |
---|---|---|---|---|
UPS-GT004990.pdf | Texto Completo | 1,73 MB | Adobe PDF | Visualizar/Abrir |
Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons