Operación resilente en redes de distribución eléctrica soterrada ante contingencias n-1 considerando criterios de calidad y confiabilidad

Para citar o enlazar este item, por favor use el siguiente identificador: http://dspace.ups.edu.ec/handle/123456789/17662
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.advisorValenzuela Santillán, Alex David-
dc.contributor.authorGanán Gaínza, Andrés Sebastián-
dc.date.accessioned2019-08-08T21:27:07Z-
dc.date.available2019-08-08T21:27:07Z-
dc.date.issued2019-08-
dc.identifier.urihttps://dspace.ups.edu.ec/handle/123456789/17662-
dc.descriptionEl presente documento presenta una propuesta para la operación resiliente de sistemas de distribución cuando ocurren fallas que colocan en estado de indisponibilidad a uno de los componentes claves de la red. Para ello, se hace uso de una metodología que busca el cambio de la topología, buscando el mejor punto de operación; considerando los criterios de calidad y de confiabilidad, realizando cálculos sucesivos de los índices más relevantes que permiten la medición de estos factores. En función de la ubicación de la contingencia y de la cantidad de centros de carga que se desconectan debido a la falla, se ensayan varios escenarios de cambio de topología por medio de simulaciones del comportamiento de la red con cada topología en software especializado, buscando que la mayor cantidad de usuarios se vuelvan a conectar hacia la red de distribución; posibilitando así la mejora de los criterios establecidos. Se pone a prueba la metodología implementada con una red de tipo soterrada que tiene implementada una compañía distribuidora con sus respectivos primarios y necesidades de demanda actuales de tal red. Se establecen varios escenarios cuyas variables son la demanda de los usuarios y la ubicación del evento de falla tipo N-1.spa
dc.description.abstractThis document presents a methodology for resilient operation of an underground distribution network. The methodology goal is the fault events that disallow one of the key components of the network. The technique seeks for changes in network that improves the network operation. It takes account of the reliability and quality criteria in order to get its goal. The method makes consecutive calculations of the most relevant index to measure the reliability and quality of the system. The methodology takes account of the contingency location and the number of loads that were disconnected from the network. Later, several changes of topology are tested. The scenarios are tested through simulations that take place under licensed software. The researchers employ the simulations in order to know the network behavior under every case. The study is looking for the case that allow to reconnect the most loads. This case will allow to improve the reliability and quality of the network. An underground network is the one employed on this document. The network is a real one and the authors employs the original topology of the feeders and the current load needs. The methodology is tested changing the load and the location of the N-1 fault.spa
dc.language.isospaspa
dc.rightsopenAccessspa
dc.rightsAtribución-NoComercial-SinDerivadas 3.0 Ecuador*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/3.0/ec/*
dc.subjectINGENIERÍA ELÉCTRICAspa
dc.subjectOPTIMIZACIÓN MATEMÁTICAspa
dc.subjectREDES ELÉCTRICASspa
dc.subjectDISTRIBUCIÓN DE ENERGÍA ELÉCTRICAspa
dc.subjectTEORÍA DE LA CONMUTACIÓNspa
dc.titleOperación resilente en redes de distribución eléctrica soterrada ante contingencias n-1 considerando criterios de calidad y confiabilidadspa
dc.typebachelorThesisspa
ups.carreraIngeniería Eléctricaspa
ups.sedeSede Quitospa
Pertenece a las colecciones: Grado

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
UPS - ST004243.pdfTexto completo2,64 MBAdobe PDFVisualizar/Abrir