Ubicación óptima de dispositivos SVC considerando el indicador de estabilidad de tensión lineal (LVSI) para mejorar el margen de estabilidad de tensión en sistemas de transmisión

Para citar o enlazar este item, por favor use el siguiente identificador: http://dspace.ups.edu.ec/handle/123456789/23534
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.advisorÁguila Téllez, Alexander-
dc.contributor.authorGarrido Castillo, Christian Paúl-
dc.date.accessioned2022-09-29T17:00:24Z-
dc.date.available2022-09-29T17:00:24Z-
dc.date.issued2022-09-
dc.identifier.urihttp://dspace.ups.edu.ec/handle/123456789/23534-
dc.descriptionEn este estudio se expone un procedimiento para el emplazamiento de compensadores SVC en el SEP mediante la técnica de clusterización difuso c-Means. Para lo cual, se empieza con la cuantificación del OPF para obtener el arreglo de sensibilidad del sistema en base al jacobiano del sistema. Luego se estiman las matrices de atenuaciones y de distancias eléctricas. Con lo cual, se emplea el algoritmo de clusterización difuso c-Means con el criterio de identificación de clústeres iniciales estimados. De esta forma, se obtienen las áreas de control de voltaje (ACV). Por otro lado, para la disposición ideal de los compensadores se emplea el criterio de minimización de los costes de instalación de los SVC junto con el índice de estabilidad de tensión lineal (LVSI). Lo cual, se aplica a cada ACV creada. La técnica descrita se aplica al esquema de 14 y 30 nodos, para comprobar su efectividad. Asimismo, los resultados obtenidos se comparan con el software Power Factory y estudios similares. Por último, la técnica propuesta demuestra ser efectiva para la creación de ACV y la disposición óptima de equipos SVC.spa
dc.description.abstractThis study presents a procedure for the placement of SVC compensators in the SEP using the fuzzy c-Means clustering technique. For which, we start with the quantification of the OPF to obtain the sensitivity array of the system based on the Jacobian of the system. Then, the attenuation and electrical distance matrices are estimated. With which, the fuzzy c-Means clustering algorithm is used with the initial estimated cluster identification criterion. In this way, the voltage control areas (VCA) are obtained. On the other hand, for the ideal arrangement of the compensators, the criterion of minimization of the installation costs of the SVCs together with the linear voltage stability index (LVSI) is used. Which is applied to each SVC created. The described technique is applied to the 14-node and 30-node scheme to check its effectiveness. Also, the results obtained are compared with the Power Factory software and similar studies. Finally, the proposed technique proves to be effective for the creation of LCAs and the optimal arrangement of SVC equipment.spa
dc.language.isospaspa
dc.rightsopenAccessspa
dc.rightsAtribución-NoComercial-SinDerivadas 3.0 Ecuador*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/3.0/ec/*
dc.subjectINGENIERÍA ELÉCTRICAspa
dc.subjectOPTIMIZACIÓN MATEMÁTICAspa
dc.subjectREGULADORES DE VOLTAJEspa
dc.subjectPOTENCIA REACTIVA (INGENIERÍA ELÉCTRICA)spa
dc.subjectESTABILIDAD EN SISTEMAS DE ENERGÍA ELÉCTRICAspa
dc.titleUbicación óptima de dispositivos SVC considerando el indicador de estabilidad de tensión lineal (LVSI) para mejorar el margen de estabilidad de tensión en sistemas de transmisiónspa
dc.typebachelorThesisspa
ups.carreraIngeniería Eléctricaspa
ups.sedeSede Quitospa
Pertenece a las colecciones: Grado

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
UPS - TTS1092.pdfTexto completo2,89 MBAdobe PDFVisualizar/Abrir


Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons Creative Commons