Metodología para reducir el desbalance de la demanda mediante sistemas de medio voltaje en corriente directa

Para citar o enlazar este item, por favor use el siguiente identificador: http://dspace.ups.edu.ec/handle/123456789/19778
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.advisorCarrión Galarza, Diego Francisco-
dc.contributor.authorSimba Reyes, Brayan David-
dc.date.accessioned2021-02-17T23:59:25Z-
dc.date.available2021-02-17T23:59:25Z-
dc.date.issued2021-02-
dc.identifier.urihttp://dspace.ups.edu.ec/handle/123456789/19778-
dc.descriptionEn la presente investigación se analizó la inclusión del sistema de media tensión en corriente directa (MVDC), en una subestación de distribución, con finalidad de solventar los problemas de desbalance de corrientes trifásicas. El estudio se hizo en consideración de abastecer de energía eléctrica a la zona residencial, por ser quien genera mayor problema de desequilibrio de corriente a la red. Con tal fin se realizaron simulaciones, por medio de diferentes escenarios de estudio que consideran demanda cambiante en función del tiempo, ejecutadas para el modelo preliminar MVDC y en el modelo de prueba del IEEE de 33 buses para distribución. Como resultado se obtuvo una media de desequilibrio de alrededor del 3.5%, en el equilibrio de la corriente, y estando dentro del rango de otras metodologías, como es el “Algoritmo de optimización dinámica” y “Cambio de fase, basado en algoritmo de murciélago modificado” que tienen una media de desequilibrio del 1.64% y 5% respectivamente. También se pudo constatar una ligera mayor capacidad de carga en el sistema con MVDC, pues se obtuvo un indicador positivo de balance en los buses del modelo IEEE de 33 buses con MVDC de 0,2218, siendo superior en comparación al 0.08 del sistema normal.spa
dc.description.abstractThis document analized the inclusion of the medium voltage system in direct current (MVDC), in a distribution substation, in order to solve the problems of unbalance of three-phase currents. The study was carried out in consideration of supplying electric power to the residential area, since it generates the greatest problem of current unbalance in the network. To this end, simulations were performed by means of different study scenarios that consider changing demand as a function of time, executed for the preliminary MVDC model and in the IEEE test model of 33 buses for distribution. As a result, an unbalance average of around 3.5% was obtained, in the balance of the current, and being within the range of other methodologies, such as the "Dynamic optimization algorithm" and "Phase shift, based on modified bat algorithm" which have an average imbalance of 1.64% and 5% respectively. Also it was possible to verify a slight higher load capacity in the system with MVDC, since a positive balance indicator was obtained in the buses of the IEEE model of 33 buses with MVDC of 0.2218, being higher compared to 0.08 of the normal system.spa
dc.language.isospaspa
dc.rightsopenAccessspa
dc.rightsAtribución-NoComercial-SinDerivadas 3.0 Ecuador*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/3.0/ec/*
dc.subjectINGENIERÍA ELÉCTRICAspa
dc.subjectANÁLISIS DE REDES ELÉCTRICASspa
dc.subjectDISTRIBUCIÓN DE ENERGÍA ELÉCTRICAspa
dc.subjectADMINISTRACIÓN DE LA DEMANDA (EMPRESAS ELÉCTRICAS)spa
dc.subjectCONSUMO DE ENERGÍA ELÉCTRICAspa
dc.subjectSISTEMAS DE ENERGÍA ELÉCTRICA­spa
dc.titleMetodología para reducir el desbalance de la demanda mediante sistemas de medio voltaje en corriente directaspa
dc.typebachelorThesisspa
ups.carreraIngeniería Eléctricaspa
ups.sedeSede Quitospa
Pertenece a las colecciones: Grado

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
UPS - TTS241.pdfTexto completo2,43 MBAdobe PDFVisualizar/Abrir


Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons Creative Commons